French utility EDF has resumed operation of unit 5 at its Bugey nuclear power plant after receiving approval from the country's nuclear safety authority. The reactor had been offline for almost two years whilst tests and repairs were carried out on its containment.

By World Nuclear News
Monday, July 31, 2017

Tests conducted in 2011 during the third ten-yearly inspection of the 880 MWe pressurized water reactor identified a high leakage rate from the inner liner of its containment. The containment was found not to be airtight owing to a corroded seal. In December 2014, Autorité de Sûreté Nucléaire (ASN) ordered more tests to be carried out during the unit's next maintenance and refuelling outage.

That outage began in August 2015 and Bugey 5 has remained offline since. Further tests indicated a degradation of the leak tightness of the metal coating of the inner liner since the tests conducted in 2011. The latest tests also helped locate the leaks at the bottom of the containment liner.

EDF informed ASN in November 2015 that it planned to make repairs to the unit's containment with a view to restarting the reactor. In April 2016, the utility submitted details of its investigation into the cause of the leaks and how it proposed to remedy them - by applying a composite coating around the base seal of the containment vessel and use a fluid "protective" lime mortar.

In late March this year, ASN approved EDF's suggested solution to repairing the containment.

EDF carried out the repairs between 29 March and 15 May 2017. The utility subsequently carried out a new test of the containment, which led to a leakage rate in compliance with the general operating rules. Last month it sent ASN a program for monitoring the effectiveness of the repairs, as well as a plan of action and investigations for searching for residual escape routes through the containment.

ASN published an information note on 24 July saying that it had agreed on 18 July that EDF could restart the unit.

EDF announced on 24 July that Bugey 5 was restarted and reconnected to then grid the previous day.

Latest News

Nuclear Refurbishment Provides Platform for Local Partnership

Friday, September 15, 2017

Brotech Precision CNC Inc. and Georgian College working together to train next generation of skilled worker

Loyalist opens nuclear classroom in downtown Port Hope

Friday, September 15, 2017

In the community that Northumberland-Peterborough South MP Kim Rudd has termed the epicentre of nuclear innovation in this country, what better location for the new Loyalist College nuclear program.

SNC-Lavalin awarded $45 million in contracts to support Bruce Power’s Life-Extension Program and reactor operations

Thursday, September 14, 2017

SNC-Lavalin (TSX: SNC) is pleased to announce it was awarded $45 million worth of contracts from February to June 2017 from Bruce Power to support its operational objectives.

Canadian Nuclear Laboratories receives OCNI Special Achievement Award

Wednesday, September 13, 2017

Canada’s national nuclear laboratory recognized by Organization of Canadian Nuclear Industries for world-class nuclear science and technology, site revitalization

Nuclear units weather Hurricane Irma

Tuesday, September 12, 2017

Two nuclear units at St Lucie were able to continue operating as Hurricane Irma made landfall in Florida. One unit at Turkey Point was shut down as a precaution in advance of the storm as nuclear operators and regulators put storm preparation procedures into action, while the other shut down automatically because of a valve-related issue.

Hurricane Harvey Makes The Case For Nuclear Power

Thursday, September 7, 2017

‘The South Texas Project reactors have been operating safely throughout Harvey and continue to do so,’ NRC spokesman Scott Burnell said.

Contact us for more information. Drop us a line!

General & Contact
Fax: (905) 839-7085
Our Address
Organization of Canadian Nuclear Industries
1550 Kingston Road, Suite 219
Pickering, Ontario L1V 1C3
Membership Enquiries & Support
Fax: (905) 839-7085